Manual #8910227 - Rev C6/095757 Phantom Dr. Ste 125 • P.O. Box 42037 • St. Louis, MO 63042(866) 240-1870 • (314) 595-6900 • FAX (800) 768-8377www.pott

Page 2 - INSTALLATION GUIDE

64.3 Mounting KeypadsPotter keypads have removable covers that allow you to easily mount the base to a wall or other at surface. After installing t

Page 3 - Table of Contents

75.1 Installing the Transformer The transformer requires an unswitched 120 VAC 60 Hz electrical outlet with at least 350mA of available current. Ne

Page 4

86.1 Battery Terminals 3 and 4Connect the black battery lead to terminal 4 on the panel and then to the negative terminal of the battery. The negati

Page 5 - Panel Specications

96.6 PFC-7500 Series Power RequirementsDuring AC power failure, the PFC-7500 Series panels, and all auxiliary devices connected to the panels, draw

Page 6 - Introduction

107.1 Terminal 5 (PFC-7501 Only)Terminal 5 supplies 12 VDC Bell Output to power alarm bells or horns. The output is rated for a maximum of 1.5 Amps.

Page 7 - System Components

1111.1 DescriptionTerminals 15 to 22 are the Class B (Style A) re zones on the PFC-7500 Series panels. These zones are suitable for connecting powe

Page 8 - 3.5 Keypads

1212.1 DescriptionThe PFC-7500 Series panels can provide two programmable auxiliary Form C (SPDT) relays when equipped with plug-in relays in socket

Page 9 - Installation

1314.3 NoticationRegistered terminal equipment must not be repaired by the user. In case of trouble, the device must be immediately unplugged from

Page 10 - 4.3 Mounting Keypads

1418.1 IntroductionFor applications that must conform to a local authorities installation standard or a National Recognized Testing Laboratory cer

Page 11 - Maintain 1/4"

1520.5 Remote Station Protective Signaling Systems60 hours of standby battery must be provided. Up to two 12 VDC, 7.0 Ah batteries may be used. See

Page 12 - Secondary Power Supply

MODEL PFC-7500/PFC-7501COMMAND PROCESSORINSTALLATION GUIDE FCC NOTICEThis equipment generates and uses radio frequency energy and, if not inst

Page 13

1622.1 SNM with NAC Extender 1K EOLR 1K EOLR1 AUX PWR2 GND3 Alarm In4 Bell PWR In5 Bell Out +6 Bell Out -7 Bell Trouble8 Bell TroubleNormal/Silence

Page 14 - Bell Output

1722.2 SNM Class B Style W using Single Notication Appliance1 AUX PWR2 GND3 Alarm In4 Bell PWR In5 Bell Out +6 Bell Out -7 Bell Trouble8 Bell Troub

Page 15 - Class B (Style A) Fire Zones

1822.3 SNM Class B Style W using Multiple Notication Appliances1 AUX PWR2 GND3 Alarm In4 Bell PWR In5 Bell Out +6 Bell Out -7 Bell Trouble8 Bell Tr

Page 16 - Form C Relay Outputs

1922.4 SNM Class B Style W Multiple Notication Appliance Circuits1 AUX PWR2 GND3 Alarm In4 Bell PWR In5 Bell Out +6 Bell Out -7 Bell Trouble8 Bell

Page 17 - Dual Phone Line Connectors

2022.9 Remote Station Reversing Relay ConnectionAC13+B5BELL6SMK11Z1A+7RED8YEL9GRN10BLK2AC4-B12Z1A-13Z1B+14Z1B-15Z2+16Z2-17Z3+18Z3-19Z4+20Z4-21Z5+22Z

Page 18 - ANSI/UL 864, NFPA 72

21AC13+B5BELL6SMK11Z1A+7RED8YEL9GRN10BLK2AC4-B12Z1A-13Z1B+14Z1B-15Z2+16Z2-17Z3+18Z3-19Z4+20Z4-21Z5+22Z5-N/ON/CCOMN/ON/CCOMJ111234J12OUTPUT 2OUTPUT 1M

Page 19

2222.11 PFC-7500 Connection to FACPAC13+B5BELL6SMK11Z1A+7RED8YEL9GRN10BLK2AC4-B12Z1A-13Z1B+14Z1B-15Z2+16Z2-17Z3+18Z3-19Z4+20Z4-21Z5+22Z5-N/ON/C COMN

Page 20 - Wiring Diagrams

23PFC-7500/7501 PROGRAMMING SHEETCOMMUNICATIONCommunication Type NONE DD 4 - 2 CID2nd Phone Line NO YESAccount Number _ _ _ _ _ (DD ran

Page 22 - SM-12/24 Module

iiiPanel Specications1.1 Power Supply ... 11.2 Communicatio

Page 23

ivForm C Relay Outputs12.1 Description ... 12Annunciator Ou

Page 24 - Fire Panel

11.1 Power SupplyPrimary Power Input: 16.5 VAC 40 VA (Model WLT wire-in) or 12/24 VDC from Fire Alarm Control Panel (FACP)Standby Battery: One or t

Page 25 - SNM Module

22.1 DescriptionThe Potter PFC-7500 Series Commercial Fire Panels are powerful 12 VDC re alarm communicators with battery backup that can also be p

Page 26 - Control Panel (FACP)

33.1 DescriptionA basic PFC-7500 Series system is made up of the alarm panel with built-in communicator, an enclosure, a 16.5 VAC wire-in transforme

Page 27

43.3 PFC-7500 Wiring DiagramThe PFC-7500 system below shows some of the accessory devices for use in various applications.AC13+B5BELL6SMK11Z1A+7RED8

Page 28

54.1 Mounting the EnclosureMount the metal enclosure for the PFC-7500 Series panels in a secure, dry place to protect the panels from damage due to